Instrumentation Cables | ||||||||||||||
EN 50288-7 Instrumentation Cables
XLPE Insulated, lsZH sheathed, cWb screened Instrumentation cables (Multipair)
RE-2X(c)H 90°c / 300V
STANDARDS
Basic design to EN 50288-7
Applications
These cables are used for transmission of analoge and digital signals in instrument and control
systems at chemistry and petr°Chemistry industry plants, power plants, natural gas and petroluem
plants, etc...
These cables are used in the environments which have no corrosive gases are emitted in the event
of fi re. In case of fi re, these cables inhibit the propagation of the fl ames whereby the development
of smoke is extremely low. Instrumentation cables are not allowed for direct connection to a low
impedance sources, e.g. public mains electricity supply. With blue sheath it is suitable for intrinsically
safe systems. These cables are not recommended for direct burial. They are for indoor and outdoor
installation, in dry and wet l°Cations; on racks, trays, in conduits.
FIRE PERFORMANCE
Flame Retardance (Single Vertical Wire Test) |
EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1* |
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)*** |
EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4 |
Halogen Free | IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1* |
No Corrosive Gas Emission | IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2* |
Minimum Smoke Emission | IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2* |
No Toxic gases | NES 02-713; NF C 20-454 |
Sunlight Resistance | UL 1581 section 1200 |
Oil Resistance** | ICEA S-73-532 |
60% of tensile strength/min.60% of elongation, *** denotes optional.
VOLTAGE RATING
300V
CABLE CONSTRUCTION
Conductor: Annealed copper solid or plain copper stranded to IEC 60228 Class 2.
Insulation: Extruded cross-linked XLPE compound, EN 50290. 2-29.
Pair:Two conductors twisted to form a pair
Lay-up: Pairs laid up in layers of optimum pitch
Separator: Polyester tape
Overall Screen: Tinned copper wire braid
Outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting
LSZH compound type SW2-SW4 as per BS 7655-2.6 can be offered.). UV resistance, hydrocarbon
resistance, oil resistance, anti rodent and anti termite properties can be offered as option.
COLOUR CODE
Insulation: Black / White, continuously numbered on white core(1, 2..)for multipair.
Outer Sheath: Black or blue for intrinsically safe systems
Physical AND THERMAL PROPERTIES
Temperature Range During Operation (Fixed State): -30°C – +70°C
Temperature Range During Installation (Mobile State): -5°C – +50°C
Minimum Bending Radius: 7.5 X Overall Diameter
CONSTRUCTION PARAMETERS
Caledonian Cable Code | RE-2X(C)H | ||
No. of Pairs x2xCross Section | Copper Weight |
Approx. Weight | |
|
No.x2xmm2 | Kg/km | Kg/km |
0.5mm2, Multipair | |||
RE-2X(C)H 2P0.5 | 2x2x0.50 | 10.7 | 143 |
RE-2X(C)H 4P0.5 | 4x2x0.50 | 11.1 | 159 |
RE-2X(C)H 5P0.5 | 5x2x0.50 | 11.9 | 181 |
RE-2X(C)H 6P0.5 | 6x2x0.50 | 13.6 | 230 |
RE-2X(C)H 8P0.5 | 8x2x0.50 | 14.2 | 264 |
RE-2X(C)H 12P0.5 | 12x2x0.50 | 16.4 | 343 |
RE-2X(C)H 16P0.5 | 16x2x0.50 | 18.2 | 418 |
RE-2X(C)H 20P0.5 | 20x2x0.50 | 19.7 | 487 |
RE-2X(C)H 24P0.5 | 24x2x0.50 | 21.1 | 557 |
0.75mm2, Multipair | |||
RE-2X(C)H 2P0.75 | 2x2x0.75 | 11.4 | 160 |
RE-2X(C)H 3P0.75 | 3x2x0.75 | 11.9 | 185 |
RE-2X(C)H 4P0.75 | 4x2x0.75 | 12.7 | 214 |
RE-2X(C)H 6P0.75 | 6x2x0.75 | 14.6 | 278 |
RE-2X(C)H 8P0.75 | 8x2x0.75 | 15.4 | 324 |
RE-2X(C)H 12P0.75 | 12x2x0.75 | 17.8 | 427 |
RE-2X(C)H 16P0.75 | 16x2x0.75 | 19.8 | 526 |
RE-2X(C)H 20P0.75 | 20.x2x0.75 | 21.5 | 623 |
RE-2X(C)H 24P0.75 | 24x2x0.75 | 23.1 | 714 |
1.0mm2, Multipair | |||
RE-2X(C)H 2P1.0 | 2x2x1.0 | 12.3 | 184 |
RE-2X(C)H 3P1.0 | 3x2x1.0 | 12.8 | 214 |
RE-2X(C)H 4P1.0 | 4x2x1.0 | 13.7 | 251 |
RE-2X(C)H 6P1.0 | 6x2x1.0 | 15.6 | 326 |
RE-2X(C)H 8P1.0 | 8x2x1.0 | 16.4 | 382 |
RE-2X(C)H 12P1.0 | 12x2x1.0 | 19.0 | 511 |
RE-2X(C)H 16P1.0 | 16x2x1.0 | 21.2 | 636 |
RE-2X(C)H 20P1.0 | 20.x2x1.0 | 23.5 | 775 |
RE-2X(C)H 24P1.0 | 24x2x1.0 | 25.3 | 892 |
1.3mm2, Multipair | |||
RE-2X(C)H 2P1.3 | 2x2x1.3 | 12.9 | 204 |
RE-2X(C)H 3P1.3 | 3x2x1.3 | 13.5 | 242 |
RE-2X(C)H 4P1.3 | 4x2x1.3 | 14.5 | 285 |
RE-2X(C)H 6P1.3 | 6x2x1.3 | 16.7 | 375 |
RE-2X(C)H 8P1.3 | 8x2x1.3 | 17.4 | 444 |
RE-2X(C)H 12P1.3 | 12x2x1.3 | 20.2 | 599 |
RE-2X(C)H 16P1.3 | 16x2x1.3 | 22.6 | 750 |
RE-2X(C)H 20P1.3 | 20x2x1.3 | 25.1 | 916 |
RE-2X(C)H 24P1.3 | 24x2x1.3 | 27.0 | 1064 |
Electrical PROPERTIES
Conductor Area Size | mm 2 | 0.5 | 0.75 | 1.0 | 1.3 | 1.5 | |
Insulation thickness (nominal) | mm | 0.4 | 0.4 | 0.4 | 0.45 | 0.45 | |
Conductor resistance (20°C) | Ω/km | 36.7 | 25 | 18.5 | 14.2 | 12.3 | |
Insulation resistance (20°C) | MΩ.km(Min.) | 5000 | |||||
Mutual Capacitance (1 kHz) | pF/m(Max.) | ||||||
≤ 4 pairs | 115 | 115 | 115 | 120 | 120 | ||
all other pairs | 90 | 90 | 90 | 90 | 90 | ||
Capacitance unbalance(1 kHz) | pF/500 m (Max.) | 300 | |||||
L / R (ratio) (max.) | μH/Ω | 25 | 25 | 25 | 40 | 40 | |
Operating voltage Urms | V | 300 | |||||
Test Voltage | Core to Core | V | 1500 | ||||
Core to Screen | V | 1500 |